Call us 24/7+86 18030182217

3500/22M Product specification

Description
The 3500/22M Transient Data Interface (TDI) is the interface
between the 3500 monitoring system and compatible
software (System 1 Condition Monitoring and Diagnostic
software and 3500 System Configuration software). The TDI
combines the function of a 3500/20 Rack Interface Module
(RIM) with the data collection capability of a communication
processor such as TDXnet.
The TDI resides in the slot adjacent to the power supplies of a
3500 rack. It interfaces with M series monitors (3500/40M,
3500/42M, etc.) to continuously collect steady state and
transient dynamic (waveform) data and pass this data
through an Ethernet link to the host software. Refer to the
Compatibility section at the end of this document for more
information.
Static data capture capability is standard with the TDI.
However, using an optional Channel Enabling Disk will allow
the TDI to capture dynamic and high-resolution transient
data as well. The TDI incorporates the communication
processor function within the 3500 rack.
Although the TDI provides certain functions common to the
entire rack, it is not part of the critical monitoring path and
has no effect on the proper, normal operation of the overall
monitor system for automatic machinery protection. Every
3500 rack requires one TDI or RIM, which always occupies
Slot 1 (next to the power supplies)

TRICONEX 3723X Product specification

Manufacturer: Triconex

Product Number: 3721

Product type: Analog input module

Voltage: 0 to 5 VDC or -5 to +5 VDC1, + 6%

Nooooo. Input points: 32 differential, DC coupling

Input update rate: 10 ms

Resolution: 12 – or 14-bit programmable

Accuracy: 0.15% of FSR at < 0° to 60° C

Common mode rejection: -85 dB (DC – 100 Hz)

Input overrange protection: 150 VDC/115 VAC continuous

Weight: 1.36 kg

Shipping weight: 4 kg

1900/65A specification

Description
The 1900/65A General Purpose Equipment Monitor is
designed to continuously monitor and protect equipment that
is used in a variety of applications and industries. The
monitor’s low cost makes it an ideal solution for general
purpose machines and processes that can benefit from
continuous monitoring and protection.
Inputs
The 1900/65A provides four transducer inputs and four
temperature inputs. Software can configure each transducer
input to support 2- and 3-wire accelerometers, velocity
sensors or proximity sensors. Each temperature input supports
Type E, J, K, and T thermocouples, and 2- or 3-wire RTDs.

Outputs
The 1900/65A provides six relay outputs, four 4-20 mA
recorder outputs, and a dedicated buffered output. The user
can use the 1900 Configuration software to configure the relay
contacts to open or close according to the OK, Alert and
Danger statuses of any channel or combination of channels,
and to provide data from any variable from any channel on any
recorder output. The dedicated buffer output can provide the
signal for each transducer input.
A Modbus Gateway option allows the monitor to provide
static variables, statuses, event list, time and date information
directly to any Modbus client, including Distributed Control
Systems (DCSs), Supervisory Control and Data Acquisition
(SCADA) systems, Programmable Logic Controllers (PLCs), or
System 1 software. The monitor uses an internal counter and a
Modbus client/master time reference to generate time and
date information. Users can upgrade monitors without the
Modbus Gateway by ordering the 1900/01 Communications
Upgrade (see the Ordering Information section). The 1900/65A

supports Modbus communications via Ethernet
and a software-configurable RS232/485 serial
port.
Configuration
The user defines monitor operation and the
Modbus Gateway register map by using
software running on a laptop or PC to create a
configuration file and download the file to the
monitor through the built-in Ethernet
connection. The 1900/65A permanently stores
configuration information in non-volatile
memory, and can upload this information to the
PC for changes.
Display Module
The 1900/65A supports an optional
display/keypad to view channel information or
make minor configuration changes. This allows
the 1900/65A to operate as a stand-alone
package. If desired, the user can mount the
display up to 75 metres (250 feet) from the
Monitor Module